Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
103
Connect the Kinetix 5700 Drive System
Chapter 5
Table 50 - Dual-axis Inverter Wiring Requirements
Dual-axis Inverter
Cat. No.
Description
Connects to Terminals
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
Pin
Signal
2198-D006-ERS
x
2198-D012-ERS
x
2198-D020-ERS
x
2198-D032-ERS
x
Motor power
(axis A and B)
Motor power cable
depends on motor/
drive combination.
0.75…2.5
(1)
(18…14)
10.0 (0.39)
0.5…0.6
(4.4…5.3)
2198-D057-ERS
x
2.5…6
(14…10)
10.0 (0.39)
0.5…0.8
(4.4…7.1)
2198-D
xxx
-ERS
x
PELV/SELV
24V power
(connector plug)
CP-1
CP-2
24V+
24V–
0.5…2.5
(20…14)
7.0 (0.28)
0.22…0.25
(1.9…2.2)
Brake power
(axis A and B)
BC-1
BC-2
MBRK+
MBRK–
N/A
(2)
DC Bus power
Bus bar
DC–
DC+
N/A
(3)
Safety
ST0-1
ST0-2
ST0-3
ST0-4
ST0-5
ST0-6
ST0-7
ST0-8
ST0-9
ST0-10
ST0-11
ST0-12
ST0-13
ST0-14
ST0-15
ST0-16
SB+ /NC
S1A
SCA
S2A
SB-
S1B
SCB
S2B
0.14…1.5
(26…16)
10.0 (0.39)
N/A
(4)
Digital inputs
IOD-1
IOD-2
IOD-3
IOD-4
IOD-5
IOD-6
IOD-7
IOD-8
IOD-9
IOD-10
IN1
COM
IN2
COM
SHLD
IN3
COM
IN4
COM
SHLD
0.14…1.5
(26…16)
10.0 (0.39)
(1) Building your own cables or using third-party cables for Kinetix VP (Bulletin VPL, VPF, VPS, and VPC-B
xxxxx
-Q) motors is not an option. Use 2090-CS
x
M1DE
single motor cables. Refer to
the Kinetix Motion Accessories Specifications Technical Data, publication
, for cable specifications.
(2) Motor brake wires are included in the Bulletin 2090 motor cable.
(3) Shared DC-bus power connections are always made from one drive module to another over the bus-bar connection system. These terminals do not receive discrete wires.
(4) This connector uses spring tension to hold wires in place.
U
V
W
U
V
W
ATTENTION:
To avoid personal injury and/or equipment damage, observe
the following:
• Make sure installation complies with specifications regarding wire types,
conductor sizes, branch circuit protection, and disconnect devices. The
National Electrical Code (NEC) and local codes outline provisions for safely
installing electrical equipment.
• Use motor power connectors for connection purposes only. Do not use them
to turn the motor on and off.
• Ground shielded power cables to prevent potentially high voltages on the
shield.