Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
Appendix B
Upgrade the Drive Firmware
The Progress dialog box
appears and updating begins.
The axis state on the LCD display changes from CONFIGURING,
STOPPED, or PRECHARGE to FIRMWARE UPDATE IN
PROGRESS, which indicates that the upgrade is in progress.
After the upgrade information
is sent to the drive, the drive
resets and performs diagnostic
checking.
14.
Wait for the Progress dialog
box to time out.
It is normal for this process to
take several minutes.
15.
Verify that the Update Status dialog box appears and indicates success or
failure as described below.
16.
Click OK.
IMPORTANT
Do not cycle power to the drive during this process or the firmware
upgrade does not complete successfully.
Upgrading Status
If
Success
Update complete appears in a GREEN Status dialog box, then go to
Failure
Update failure appears in a RED Status dialog box, then refer to the
ControlFLASH Firmware Upgrade Software User Manual, publication
for troubleshooting information.
IMPORTANT
If you are upgrading a feedback-only axis and you checked Inhibit
Module on the Connection category in Module Properties, you must clear
the Inhibit Module checkbox before resuming normal operation.