Chapter 6
Configure and Start the Kinetix 5700 Drive System
Figure 100 - Group 2 Single-axis Inverter Configuration
Figure 101 - Group 2 Dual-axis Inverter Configuration
Test and Tune the Axes
This procedure assumes that you have configured your Kinetix 5700 drive,
your Logix5000 controller, and applied power to the system.
For help using the Logix Designer application as it applies to testing and tuning
your axes with ControlLogix EtherNet/IP modules or CompactLogix 5370
controllers, refer to
.
For testing and tuning iTRAK movers, see the iTRAK System User Manual,
publication
.
Test the Axes
Follow these steps to test the axes.
1.
Verify the load was removed from each axis.
IMPORTANT
Before proceeding with testing and tuning your axes, verify that the MOD
and NET status indicators are operating as described in
.
ATTENTION:
To avoid personal injury or damage to equipment, you
must remove the load from each axis as uncontrolled motion can
occur when an axis with an integral motor brake is released during
the test.