44
Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
Chapter 2
Plan the Kinetix 5700 Drive System Installation
Cable Categories for Kinetix 5700 Systems
These tables indicate the zoning requirements of cables connecting to the
Kinetix 5700 drive system components.
Table 9 - DC-bus Power Supplies
Table 10 - Dual-axis and Single-axis Inverters
Wire/Cable
Connector
Zone
Method
Very Dirty
Dirty
Clean
Ferrite Sleeve
Shielded Cable
L1, L2, L3 (shielded cable)
IPD
X
X
L1, L2, L3 (unshielded cable)
X
DC-/DC+ (DC bus)
DC
Bus-bar only, no wiring connector.
DC+/SH (shunt)
RC
X
CONT EN- and CONT EN+ (M1 contactor)
CED
X
24V DC
CP
X
Registration input, greater than 30 m (98.4 ft)
IOD
X
X
Registration input, less than 30 m (98.4 ft)
X
Ethernet (shielded cable
PORT1
PORT2
X
X
Wire/Cable
Connector
Zone
Method
Very Dirty
Dirty
Clean
Ferrite Sleeve
Shielded Cable
DC-/DC+ (DC bus)
DC
Bus-bar only, no wiring connector.
U, V, W (motor power)
Motor feedback
Motor brake
Kinetix VP
motors
MP
MF
BC
X
X
X
X
X
X
U, V, W (motor power)
Motor feedback
Motor brake
MP-Series™
motors
MP
MF or UFB
BC
X
X
X
X
X
X
24V DC
CP
X
Safety enable for safe torque-off (hardwired)
STO
X
Registration input, greater than 30 m (98.4 ft)
IOD
X
X
Registration input, less than 30 m (98.4 ft)
X
Ethernet
PORT1
PORT2
X
X