Kinetix 5700 Safe Torque-off Function
Troubleshoot the Safe Torque-off Function
Table 131 - Kinetix 5700 Hardwired STO Troubleshooting
illustrates when the safe torque-off mismatch is detected and
GuardStopInputFault is posted.
Figure 105 - System Operation when Safety Enable Inputs Mismatch Occurs
Exception Code on Drive Display
Fault Message
Logix Designer
Problem
Possible Solutions
SAFE FLT 09 - SS IN
GuardStopInputFault
Safe torque-off function mismatch.
System does not allow motion. Safe
torque-off mismatch is detected when
safety inputs are in a different state for
more than 1.0 second.
• Verify safety wiring and connections:
– Wire terminations at safe torque-off (STO) connector
– Cable/header not seated correctly
– +24V power
• Check state of safety inputs.
• Reset error and run proof test.
• If error persists, return the drive to Rockwell Automation.
SAFE FLT S01- Safety Core Internal
SafetyCoreFault
Drive safety diagnostic detected internal
STO design failure.
• Cycle control power
• Return drive for repair if fault continues
SAFE FLT S03 - Gate Drive
GuardGateDriveFault
(1)
Drive safety diagnostic detected internal
STO design failure.
• Cycle control power
• Execute STO function
• Return drive for repair if fault continues
SAFE FLT S03 - Safe Torque Off Fault
SafeTorqueOffFault
Hardwired input received while in
integrated safety mode.
Reset the drive to the out-of-box safety state (Hardwired STO
mode). See
for more information.
(1) Displayed in the Quick View Pane as Safety Fault.
Safety Input S1
Safety Input S2
GuardFault
SafeTorqueOffInhibit
Start Inhibited
GuardOKStatus
OK
GuardGateDriveOutputStatus
Torque Disabled
Stop Requested
GuardStopInputStatus
GuardStopRequestsStatus
GuardStopInputFault
No Fault
1 Second Descrepancy Limit
No Fault
Faulted
Not OK
Faulted