360
Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
Appendix D
Motor Control Feature Support
Phase-loss Detection Attributes
Phase-loss Detection Configuration
Follow these steps to configure the phase-loss detection attributes.
1.
In the Controller Organizer, right-click an axis and choose Properties.
2.
Select the Parameter List category and scroll to ProvingConfiguration.
3.
From the ProvingConfiguration pull-down menu, choose Enabled to
enable the torque proving feature.
4.
Enter a value in the TorqueProveCurrent attribute appropriate for your
application.
5.
Click OK.
The TorqueProveCurrent attribute is active only if ProvingConfiguration is set
to Enabled. TorqueProveCurrent lets you specify the amount of current that is
used during the torque proving test and calculated as a percentage of motor
ID
Access
Attribute
Conditional Implementation
590
SSV
Proving Configuration
0 = Disabled
1 = Enabled
591
SSV
Torque Prove Current
% Motor Rated
Units: Amps
Default: 0.000
Min/Max: 0/10,000