Interconnect Diagrams
Appendix A
Passive Shunt Resistor
Wiring Examples
Wiring from the Bulletin 2198 shunt modules and resistor are made directly to
the shunt (RC) connector. You can configure either of the DC-bus power
supply digital inputs as Shunt Thermal Switch OK in the Logix Designer
application. Refer to
to see how the DC-bus power supply Digital
Input category is configured.
Figure 136 - DC-bus Power Supply with External Passive Shunt Module
Figure 137 - DC-bus Power Supply with External Passive Shunt Resistor
Refer to the Kinetix 5700 Passive Shunt Module Installation Instructions,
publication
, for additional installation information.
IMPORTANT
Before wiring the Bulletin 2198 external shunt to the RC connector, remove
the wires from the internal servo-drive shunt. Do not connect both internal
and external shunt resistors to the DC-bus power supply.
ATTENTION:
To avoid damage to the Kinetix 5700 drive system, wire the
2198-R014, 2198-R031, or 2198-R127 shunt thermal switch to a digital input
on the DC-bus power supply and configure the Shunt Thermal Switch OK
function in the Logix Designer application.
DC+
SH
R1
R2
IN1
COM
IN2
SHLD
1
2
3
4
24V DC
2198-P
xxx
DC-bus Power Supply
Shunt (RC)
Connector
Internal Shunt
2198-R014, 2198-R031,
and 2198-R127 External
Passive Shunt Module
Resistor
Thermal Switch
Digital Input
(IOD) Connector
DC+
SH
2198-P
xxx
DC-bus Power Supply
Shunt (RC)
Connector
Internal Shunt
2198-R004 External
Passive Shunt Resistor