Connect the Kinetix 5700 Drive System
Chapter 5
Wire the Contactor Enable Connector
The contactor-enable (CED) connector applies to only the DC-bus power
supply.
Figure 67 - CED Connector Wiring - Connector Plug
Table 54 - Contactor-enable (CED) Connector Plug Specifications
ATTENTION:
Wiring the contactor-enable relay is required. To avoid personal
injury or damage to the Kinetix 5700 drive system, wire the contactor-
enable relay into your control string so that:
• three-phase power is removed and the DC-bus power supply is protected
under various fault conditions.
• three-phase power is never applied to the Kinetix 5700 drive system before
control power is applied.
MOD–
NET–
2
1
1
4
I/O
EN–
EN+
Contactor-enable (CED) Connector Plug
2198-P
xxx
DC-bus Power Supply
(front view)
DC-bus Power Supply
Cat. No.
Pin
Signal
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
2198-P031
2198-P070
2198-P141
2198-P208
EN–
EN+
CONT EN–
CONT EN+
0.14…2.5
(26…12)
7.0 (0.28)
0.4…0.5
(3.5…4.4)