Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
163
Configure and Start the Kinetix 5700 Drive System
Chapter 6
Continue Inverter Configuration
After you’ve established your Kinetix 5700 inverters in the Logix Designer
application, the feedback options need to be defined for each axis. Each
physical axis supports motor and auxiliary feedback.
Table 91 - Kinetix 5700 Feedback Axis Summary
Follow these steps to configure the axes for your Kinetix 5700 drive system.
1.
Right-click the 2198-
xxxx
-ERS4 inverter you just created and choose
Properties.
The Module Properties dialog box appears.
2.
Select the Associated Axes category.
In this 2198-D006-ERS4 (dual-axis inverter) example, four axes are
possible. Single-axis inverters support only two axes.
• Axis 1 and Axis 2 apply to Motor (DSL) Feedback Connector A
(Port 1) and Universal Feedback Connector A (Port 1).
• Axis 3 and Axis 4 apply to Motor (DSL) Feedback Connector B
(Port 2) and Universal Feedback Connector B (Port 2).
Kinetix 5700 Inverter
Inverter Cat. No.
Motor Feedback
Auxiliary Feedback
Single-axis Inverters
2198-S
xxx
-ERS3 or
2198-S
xxx
-ERS4
1 (axis 1)
1 (axis 2)
Dual-axis Inverters
2198-D
xxx
-ERS3 or
2198-D
xxx
-ERS4
2 (axis 1 and 3)
2 (axis 2 and 4)