282
Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
Appendix A
Interconnect Diagrams
In this example, the DC-bus power supply 24V input wiring connector and the
three iTRAK power supply 24V input wiring connectors are wired separately.
The 2198T-W25K-P-IN input wiring connector is rated for 41 A. See
Appendix C on
to determine 24V input power requirements needed
to design proper distribution for 24V control power.
Figure 129 - Kinetix 5700 Drives (multiple iTRAK power supply) Configuration
EN+
EN–
+24V
24V_COM
+24V
24V_COM
2
1
DC+
DC-
DC+
DC-
DC+
SH
CONT EN+
CONT EN–
L3 L2 L1
+24V
24V_COM
DC+
DC-
+24V
24V_COM
DC+
DC-
Bonded Cabinet
Ground Bus *
Control Power
(CP) Connectors
Chassis
Customer Supplied
+24V DC
Power Supply *
DC Bus
(DC) Connectors
2198-P141
Kinetix 5700
DC-bus Power Supply
2198T-W25K-ER
Kinetix 5700
iTRAK Power Supply
Contactor Enable
(CED) Connector
2198T-W25K-P-T
T-connectors and Bus Bars
Shunt Power
(RC) Connector
2198-TCON-24VDCIN36
24V Input Power
Wiring Connector
PE Ground
Note 9
* Indicates User Supplied Component
Refer to
Attention
statement (Note 14).
STOP *
START *
CR1 *
CR1 *
CR1 *
M1 *
24V AC/DC or
120/240V AC
50/60 Hz
Refer to table on
for note information.
Grounding Screws/Jumpers
Note 12
Internal Shunt
Note 11
2198T-W25K-ER
Kinetix 5700
iTRAK Power Supply
2198T-W25K-ER
Kinetix 5700
iTRAK Power Supply
PE Ground
Note 9
PE Ground
Note 9
2198T-W25K-P-T
T-connectors and Bus Bars
2198T-W25K-P-IN
24V Input Power
Wiring Connector
324…528V AC rms
Three-phase Input
Notes 1, 2, 3
Three-phase Input
(IPD) Connectors
Circuit Protection*
Note 2
2198-DB290-F
Three-phase
AC Line Filter
Note 4
1321-3R
x
80-B *
Line Reactors
(required components)
M1 Contactor*
Note 10
PE Ground
Note 9
Bonded Cabinet
Ground Bus *
Bonded Cabinet
Ground Bus *