Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
131
Connect the Kinetix 5700 Drive System
Chapter 5
Capacitor Module
Connections
Follow these guidelines when wiring the 2198-CAPMOD-2240 capacitor
module and 2198-CAPMOD-DCBUS-IO extension module:
• Wire module status (MS) relay output connections to digital input Bus
Capacitor OK or the Logix5000™ controller (optional).
• Refer to
wiring example on
• Refer to
Kinetix 5700 Capacitor Module Status Indicators
for troubleshooting the module status indicators and relay output.
• Refer to the installation instructions provided with your Kinetix 5700
capacitor module, publication
.
Figure 87 - Capacitor Module Features and Indicators
IMPORTANT
To improve system performance, run wires and cables in the wireways as
established in
. Connections to the DC bus must be made with the
shared-bus connection system.
MODULE
STATUS
MOD
DC BUS
8
24V–
24V+
2
3
4
1
7
6
24V–
24V+
10
9
12
11
5
5700
2198-CAPMOD-2240
Capacitor Module
(front view)
2198-CAPMOD-2240 Capacitor Module
(top views)
2198-CAPMOD-2240
Capacitor Module
(side view, lug cover removed)
Item
Description
Item
Description
1
Ground stud
7
DC-bus (DC) connector
2
Module status (MS) connector
8
24V control input power (CP) connector
3
DC-bus status indicator
9
DC– M8 stud (external DC-bus)
4
Module status indicator
10
DC+ M8 stud (external DC-bus), shown with wire lug
5
Stud/lug cover with wires
(1)
11
M8 hex nut
6
Stud cover without wires
12
Lug spacer
(1) This example shows the lug cover oriented for wires exiting to the left (capacitor module is on the far left of the drive
configuration). Rotate lug cover 180° when wires exit to the right (capacitor module is on the far right of the drive
configuration).