Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
Chapter 2
Plan the Kinetix 5700 Drive System Installation
Input Power UL/CSA Circuit-protection Specifications
Input Power IEC (non-UL/CSA) Circuit-protection Specifications
Contactor Specifications
The DC-bus power supply contactor enable relay (CED connector) is rated at
24V DC or 110/220V AC at 1.0 A, max.
Table 7 - Input Power Contactor Specifications
Refer to the Kinetix Servo Drives Technical Data, publication
for additional power specifications for your DC-bus power supply.
Kinetix 5700 Drives
UL/CSA Applications
(1)
DC-bus Power Supply
Cat. No.
Drive Voltage
(three-phase) nom
Bussmann Fuses
Cat. No.
Miniature CB
Cat. No.
Motor Protection CB,
Self Protected CMC
Cat. No.
Molded Case CB
Cat. No.
2198-P031
324…528V AC
LPJ-15SP (15A)
1489-M3D250
140M-D8E-C25
140G-G6C3-C25
2198-P070
LPJ-40SP (40A)
1489-M3D400
140M-F8E-C45
140G-G6C3-C50
2198-P141
LPJ-70SP (70A)
1489-M3D630
N/A
140G-G6C3-C90
2198-P208
LPJ-100SP (100A)
N/A
N/A
140G-G6C3-D12
(1) For applications requiring CSA certification, fuses (Bussmann catalog number 170M1760) must be added to the DC link between the two drive clusters when circuit breakers are used for branch circuit
protection. The DC bus fuses are not required when AC line fuses are used for branch circuit protection.
Kinetix 5700 Drives
IEC (non-UL/CSA) Applications
DC-bus Power Supply
Cat. No.
Drive Voltage
(three-phase) nom
DIN gG Fuses
Amps, max
Miniature CB
Cat. No.
Motor Protection CB
Cat. No.
Molded Case CB
Cat. No.
2198-P031
324…528V AC
16
1489-M3D250
N/A
140M-D8E-C25
140G-G6C3-C25
2198-P070
40
N/A
1492-SPM3D400
140M-F8E-C45
140G-G6C3-C50
2198-P141
75
N/A
1492-SPM3D630
140MG-H8E-C60
140G-G6C3-C90
2198-P208
110
N/A
N/A
140MG-H8E-D10
140G-G6C3-D12
DC-bus Power Supply
Cat. No.
Contactor
(1)
(2)
Cat. No.
Intermediate Relay
(3)
Cat. No.
2198-P031
100-C16EJ10
N/A
2198-P070
100-C37EJ10
2198-P141
100-C72DJ10
700-HB32Z24 (relay)
700-HN153 (socket)
2198-P208
100-C97DJ10
2198-P208 (2 in parallel)
100-D180EZJ10
2198-P208 (3 in parallel)
100-D300EZJ10
(1) Auxiliary contact configuration (10) is for 1 N.O. 0 N.C. Other configurations are available.
(2) Requires integrated diode with the contactor coil.
(3) These DC-bus power supplies require an additional intermediate relay used with the contactor.