Configure and Start the Kinetix 5700 Drive System
The Logix Designer - Motor and Feedback Test dialog box appears. The
Test State is Executing. TESTING appears on the drive LCD display.
When the test completes successfully, the Test State changes from
Executing to Passed.
7.
Click OK.
This dialog box appears asking if
the axis moved in the forward
direction.
8.
Click Yes if you agree.
9.
Click Accept Test Results.
10.
If the test fails, this dialog box
appears.
a. Click OK.
b. Verify the DC bus voltage.
c. Verify unit values entered in the
Scaling category.
d. Verify the motor power and feedback wiring.
e. Return to
and run the test again.
TESTING
192.168.1.1
DC BUS: 680.0V
Drive LCD Display