Chapter 6
Configure and Start the Kinetix 5700 Drive System
Table 81 - Navigating the Inverter Settings Menu
Settings Menu Selections
Sub Menu Selections
Attributes
Default
Description
Protected Mode
Reset
ENABLED
DISABLED
ENABLED
When Enabled (default), identity object or
safety resets are not possible when a
controller connection is open.
Network Config
ENABLED
DISABLED
ENABLED
When Enabled (default), network
configuration changes are not possible when
a controller connection is open.
Flash Update
ENABLED
DISABLED
ENABLED
When Enabled (default), firmware updates
are not possible when a controller
connection is open.
Device Config
ENABLED
DISABLED
ENABLED
When Enabled (default), only attribute
writes are possible when a controller
connection is open.
Network
->Static IP
(1)
IP address
192.168.1.1
Indicates current IP address
Subnet mask
255.255.255.000
Indicates current subnet mask
Gateway
192.168.001.001
Indicates current gateway
DHCP
On
Turns DHCP on
Off
Turns DHCP off
Display
Backlight Timeout
30 sec…NEVER
(NEVER=no timeout period,
the backlight is always on)
-> 3 min
Sets backlight timeout period of the display
Cyclic Data Select
(2)
DC bus voltage
INV UTIL
Inverter utilization in percent
INV TEMP
Inverter temperature in °C
MOTOR UTIL
Motor utilization in percent
SPEED
RPM
OUT PWR
Output power in watts
OUT FREQ
Output frequency in hertz
OUT CUR
Output current in amps
Set Contrast
-10…+10
0
Contrast setting of the display
Safety
Reset Ownership
Are you sure?
Resets safety ownership
(reset fails after 30 seconds)
Web
Enabled
Enables the web server
->Disabled
Disables the web server
(1) An arrow (->) appears in front of the chosen attribute indicating that this attribute is currently configured. This is also the factory default setting.
(2) The DC bus voltage is one of several cyclic data attributes. You can select any of the Cyclic Data Select attributes to be displayed on the Home screen.