6 - 73
Chapter 6 Sequence Program Used for Positioning Control
6.5.6 Stop program
The axis stop signal or stop signal from external input signal is used to stop the control.
Create a program to turn ON the axis stop signal as the stop program.
Signal
LD77MS2
LD77MS4
LD77MS16
Axis stop signal
Y4, Y5
Y4, Y5, Y6, Y7
Cd.180
Axis stop
Each control is stopped in the following cases.
(1) When each control is completed normally
(2) When the servo READY signal is turned OFF
(3) When a PLC CPU error occurs
(4) When the PLC READY signal is turned OFF
(5) When an error occurs in the Simple Motion module
(6) When control is intentionally stopped (Stop signal from PLC CPU turned ON, etc.)
The outline for the stop process in above cases is shown below. (Excluding "(1) When
each control is completed normally" above.)
Refer to Section 12.1 "Speed-torque control" for the stop process during the speed
control mode, torque control mode and continuous operation to torque control mode.
[1] Stop
process
Stop cause
Stop
axis
M code
ON signal
after stop
Axis operation
status after
stopping
(
Md.26
)
Stop process
OPR control
Major
positioning
control
High-level
positioning
control
Manual control
Machine
OPR control
Fast OPR
control
JOG/
Inching
operation
Manual pulse
generator
operation
Forced stop
"Forced stop input
signal" OFF from an
external device
All
axes
No change Servo OFF
Immediate stop
For the stop method of the servo amplifier, refer to each servo
amplifier instruction manual.
Servo READY OFF
• Servo amplifier
power supply OFF Each
axis
No change
Servo amplifier
has not been
connected
• Servo alarm
Error
• Forced stop input
to servo amplifier
Servo OFF
Fatal stop
(Stop group 1)
Hardware stroke limit
upper/lower limit
error occurrence
Each
axis
No change Error
Deceleration stop/sudden stop
(Select with
"
Pr.37
Stop group 1 sudden stop selection
"
.)
Deceleration
stop
Emergency stop
(Stop group 2)
Error occurs in PLC
CPU
All
axes
No change
Error
Delegation stop/sudden stop
(Select with
"
Pr.38
Stop group 2 sudden stop selection
"
.)
Deceleration
stop
PLC READY signal
OFF
Turns OFF
Error in test mode
No change
Relatively safe stop
(Stop group 3)
Axis error detection
(Error other than stop
group 1 or 2)
Each
axis
No change Error
Deceleration stop/sudden stop
(Select with
"
Pr.39
Stop group 3 sudden stop selection
"
.)
Deceleration
stop
Intentional stop
(Stop group 3)
"Axis stop signal" ON
from PLC CPU
Each
axis
No change
Stopped
(Standby)
"Stop" input from GX
Works2
Содержание MELSEC-L Series
Страница 1: ...MELSEC L LD77MS Simple Motion Module User s Manual Positioning Control LD77MS2 LD77MS4 LD77MS16 ...
Страница 2: ......
Страница 30: ...MEMO ...
Страница 70: ...2 10 Chapter 2 System Configuration MEMO ...
Страница 83: ...3 13 Chapter 3 Specifications and Functions MEMO ...
Страница 103: ...3 33 Chapter 3 Specifications and Functions MEMO ...
Страница 107: ...3 37 Chapter 3 Specifications and Functions MEMO ...
Страница 111: ...3 41 Chapter 3 Specifications and Functions MEMO ...
Страница 115: ...3 45 Chapter 3 Specifications and Functions MEMO ...
Страница 140: ...4 22 Chapter 4 Installation Wiring and Maintenance of the Product MEMO ...
Страница 253: ...5 113 Chapter 5 Data Used for Positioning Control MEMO ...
Страница 342: ...5 202 Chapter 5 Data Used for Positioning Control MEMO ...
Страница 438: ...7 20 Chapter 7 Memory Configuration and Data Process MEMO ...
Страница 440: ...MEMO ...
Страница 485: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Страница 594: ...9 134 Chapter 9 Major Positioning Control MEMO ...
Страница 624: ...10 30 Chapter 10 High Level Positioning Control MEMO ...
Страница 656: ...11 32 Chapter 11 Manual Control MEMO ...
Страница 690: ...12 34 Chapter 12 Expansion Control MEMO ...
Страница 798: ...13 108 Chapter 13 Control Sub Functions MEMO ...
Страница 866: ...14 68 Chapter 14 Common Functions MEMO ...
Страница 884: ...15 18 Chapter 15 Dedicated Instructions MEMO ...
Страница 899: ...16 15 Chapter 16 Troubleshooting MEMO ...
Страница 1036: ...Appendix 88 Appendices MEMO ...
Страница 1039: ......