Parameter
Values (Range)
Unit
Step
Default
Description
Sixth reclose time
0...300000
ms
10
5000
Dead time for CBB6
Seventh reclose time
0...300000
ms
10
5000
Dead time for CBB7
Init signals CBB1
0...63
1
0
Initiation lines for CBB1
Init signals CBB2
0...63
1
0
Initiation lines for CBB2
Init signals CBB3
0...63
1
0
Initiation lines for CBB3
Init signals CBB4
0...63
1
0
Initiation lines for CBB4
Init signals CBB5
0...63
1
0
Initiation lines for CBB5
Init signals CBB6
0...63
1
0
Initiation lines for CBB6
Init signals CBB7
0...63
1
0
Initiation lines for CBB7
Shot number CBB1
0...5
1
0
Shot number for CBB1
Shot number CBB2
0...5
1
0
Shot number for CBB2
Shot number CBB3
0...5
1
0
Shot number for CBB3
Shot number CBB4
0...5
1
0
Shot number for CBB4
Shot number CBB5
0...5
1
0
Shot number for CBB5
Shot number CBB6
0...5
1
0
Shot number for CBB6
Shot number CBB7
0...5
1
0
Shot number for CBB7
Frq Op counter limit
0...250
1
0
Frequent operation counter lockout limit
Frq Op counter time
1...250
min
1
1
Frequent operation counter time
Frq Op recovery time
1...250
min
1
1
Frequent operation counter recovery time
Auto init
0...63
1
0
Defines INIT lines that are activated at
auto initiation
Table 472:
DARREC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Manual close mode
0=False
1=True
0=False
Manual close mode
Wait close time
50...10000
ms
50
250
Allowed CB closing time after reclose
command
Max wait time
100...1800000
ms
100
10000
Maximum wait time for BLK_RECL_T
release
Max trip time
100...10000
ms
100
10000
Maximum wait time for deactivation of
protection signals
Max Thm block time
100...1800000
ms
100
10000
Maximum wait time for thermal blocking
signal deactivation
Cut-out time
0...1800000
ms
100
10000
Cutout time for protection coordination
Dsr time shot 1
0...10000
ms
100
0
Discrimination time for first reclosing
Dsr time shot 2
0...10000
ms
100
0
Discrimination time for second reclosing
Dsr time shot 3
0...10000
ms
100
0
Discrimination time for third reclosing
Dsr time shot 4
0...10000
ms
100
0
Discrimination time for fourth reclosing
Auto wait time
0...60000
ms
10
2000
Wait time for reclosing condition fullfilling
Auto lockout reset
0=False
1=True
1=True
Automatic lockout reset
Table continues on next page
1MRS757454 D
Section 8
Control functions
611 series
435
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......