Table 306:
PSPTUV Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Voltage block value
0.01...1.00
xUn
0.01
0.20
Internal blocking level
Enable block value
0=False
1=True
1=True
Enable Internal Blocking
Table 307:
PSPTUV Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 308:
PSPTUV Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Relative hysteresis
1.0...5.0
%
0.1
4.0
Relative hysteresis for operation
4.5.5.8
Monitored data
Table 309:
PSPTUV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
PSPTUV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.5.5.9
Technical data
Table 310:
PSPTUV Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 0.99 × set
Start
value
U
Fault
= 0.9 × set
Start
value
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set
Relative hysteresis
Table continues on next page
Section 4
1MRS757454 D
Protection functions
280
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......