6.2.10
Technical data
Table 388:
HZCCxSPVC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the current
measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Reset time
<40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
6.2.11
Technical revision history
Table 389:
HZCCxSPVC Technical revision history
Technical revision
Change
B
Function name changed from HZCCRDIF to
HZCCASPVC, HZCCBSPVC, HZCCCSPVC.
6.3
Runtime counter for machines and devices MDSOPT
6.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Runtime counter for machines and
devices
MDSOPT
OPTS
OPTM
6.3.2
Function block
GUID-C20AF735-FF25-411B-9EA6-11D595484613 V3 EN
Figure 170:
Function block
6.3.3
Functionality
The runtime counter for machines and devices function MDSOPT calculates and
presents the accumulated operation time of a machine or device as the output. The unit
of time for accumulation is hour. The function generates a warning and an alarm when
Section 6
1MRS757454 D
Supervision functions
346
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......