Table 272:
PHPTOV Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate time
40...60000
ms
1
40
Minimum operate time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Curve Sat Relative
0.0...10.0
0.1
0.0
Tuning parameter to avoid curve
discontinuities
Relative hysteresis
1.0...5.0
%
0.1
4.0
Relative hysteresis for operation
4.5.1.9
Monitored data
Table 273:
PHPTOV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
PHPTOV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.5.1.10
Technical data
Table 274:
PHPTOV Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 1.1 × set
Start
value
23 ms
27 ms
31 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set
Relative hysteresis
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1)
Start value = 1.0 × U
n
, Voltage before fault = 0.9 × U
n
, f
n
= 50 Hz, overvoltage in one phase-to-phase
with nominal frequency injected from random phase angle, results based on statistical distribution of
1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Start value = 1.20 × U
n
,
Start value multiples in range of 1.10...2.00
1MRS757454 D
Section 4
Protection functions
611 series
259
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......