Description
Type test value
Reference
Pulse magnetic field immunity
test
1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic
field immunity test
IEC 61000-4-10
•
2 s
100 A/m
•
1 MHz
400 transients/s
Voltage dips and short
interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Power frequency immunity test
Binary inputs only
IEC 61000-4-16
IEC 60255-26, class A
•
Common mode
300 V rms
•
Differential mode
150 V rms
Conducted common mode
disturbances
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
IEC 61000-4-16
Emission tests
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
•
Conducted
0.15...0.50 MHz
<79 dB (µV) quasi peak
<66 dB (µV) average
0.5...30 MHz
<73 dB (µV) quasi peak
<60 dB (µV) average
•
Radiated
30...230 MHz
<40 dB (µV/m) quasi peak,
measured at 10 m distance
230...1000 MHz
<47 dB (µV/m) quasi peak,
measured at 10 m distance
1…3 GHz
<76 dB (µV/m) peak
<56 dB (µV/m) average,
measured at 3 m distance
3…6 GHz
<80 dB (µV/m) peak
<60 dB (µV/m) average,
measured at 3 m distance
Section 13
1MRS757454 D
Protection relay and functionality tests
518
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......