The operation of INRPHAR can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
A070694 V2 EN
Figure 142:
Functional module diagram
I_2H/I_1H
This module calculates the ratio of the second harmonic (I_2H) and fundamental
frequency (I_1H) phase currents. The calculated value is compared to the set
Start
value
. If the calculated value exceeds the set
Start value
, the module output is
activated.
Level detector
The output of the phase specific level detector is activated when the fundamental
frequency current I_1H exceeds five percent of the nominal current.
Timer
Once activated, the timer runs until the set
Operate delay time
value. The time
characteristic is according to DT. When the operation timer has reached the
Operate
delay time
value, the
BLK2H
output is activated. After the timer has elapsed and the
inrush situation still exists, the
BLK2H
signal remains active until the I_2H/I_1H ratio
drops below the value set for the ratio in all phases, that is, until the inrush situation is
over. If the drop-off situation occurs within the operate time up counting, the reset
timer is activated. If the drop-off time exceeds
Reset delay time
, the operate timer is
reset.
The
BLOCK
input can be controlled with a binary input, a horizontal communication
input or an internal signal of the relay program. The activation of the
BLOCK
input
prevents the
BLK2H
output from being activated.
Section 5
1MRS757454 D
Protection related functions
304
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......