7.1.4.2
Function block
A070777 V2 EN
Figure 175:
Function block
7.1.4.3
Signals
Table 401:
CMMXU Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
Table 402:
CMMXU Output signals
Name
Type
Description
HIGH_ALARM
BOOLEAN
High alarm
HIGH_WARN
BOOLEAN
High warning
LOW_WARN
BOOLEAN
Low warning
LOW_ALARM
BOOLEAN
Low alarm
7.1.4.4
Settings
Table 403:
CMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required by limit
supervision
A high high limit
0.00...40.00
xIn
1
1.40
High alarm current limit
A high limit
0.00...40.00
xIn
1
1.20
High warning current limit
A low limit
0.00...40.00
xIn
1
0.00
Low warning current limit
A low low limit
0.00...40.00
xIn
1
0.00
Low alarm current limit
A deadband
100...100000
1
2500
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Section 7
1MRS757454 D
Measurement functions
360
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......