7.1.6.4
Settings
Table 417:
RESCMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
A Hi high limit res
0.00...40.00
xIn
1
0.20
High alarm current limit
A high limit res
0.00...40.00
xIn
1
0.05
High warning current limit
A deadband res
100...100000
1
2500
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Table 418:
RESCMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
7.1.6.5
Monitored data
Table 419:
RESCMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
Io-A
FLOAT32
0.00...40.00
xIn
Measured residual
current
BLOCK
BOOLEAN
0=False
1=True
Block signal for all binary
outputs
HIGH_ALARM
BOOLEAN
0=False
1=True
High alarm
HIGH_WARN
BOOLEAN
0=False
1=True
High warning
I_INST_RES
FLOAT32
0.00...40.00
xIn
Residual current
Amplitude, magnitude of
instantaneous value
I_ANGL_RES
FLOAT32
-180.00...180.00
deg
Residual current angle
I_DB_RES
FLOAT32
0.00...40.00
xIn
Residual current
Amplitude, magnitude of
reported value
I_DMD_RES
FLOAT32
0.00...40.00
xIn
Demand value of residual
current
I_RANGE_RES
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Residual current
Amplitude range
Max demand Io
FLOAT32
0.00...40.00
xIn
Maximum demand for
residual current
Table continues on next page
Section 7
1MRS757454 D
Measurement functions
368
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......