Table 326:
STTPMSU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=IIt
2=IIt, CB
3=IIt + stall
4=IIt + stall, CB
1=IIt
Motor start-up operation mode
Counter Red rate
2.0...250.0
s/h
0.1
60.0
Start time counter reduction rate
Cumulative time Lim
1...500
s
1
10
Cumulative time based restart inhibit limit
Emg start Red rate
0.00...100.00
%
0.01
20.00
Start time reduction factor when
emergency start is On
Restart inhibit time
0...250
min
1
30
Time delay between consecutive startups
Ini start up counter
0...999999
1
0
Initial value for the START_CNT
Table 327:
STTPMSU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Motor standstill A
0.05...0.20
xIn
0.01
0.12
Current limit to check for motor standstill
condition
4.7.8
Monitored data
Table 328:
STTPMSU Monitored data
Name
Type
Values (Range)
Unit
Description
START_CNT
INT32
0...999999
Number of motor start-
ups occurred
START_TIME
FLOAT32
0.0...999.9
s
Measured motor latest
startup time in sec
T_ST_CNT
FLOAT32
0.0...99999.9
s
Cumulated start-up time
in sec
T_RST_ENA
INT32
0...999
min
Time left for restart when
lockstart is enabled in
minutes
IIT_RL
FLOAT32
0.00...100.00
%
Thermal stress relative to
set maximum thermal
stress
STALL_RL
FLOAT32
0.00...100.00
%
Start time relative to the
operate time for stall
condition
STTPMSU
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 4
1MRS757454 D
Protection functions
300
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......