A070867 V1 EN
Figure 196:
Signal scheme of autoreclosing operation initiated with protection
start signal
The autoreclosing shot is initiated with a start signal of the protection function after the
start delay time has elapsed. The autoreclosing starts when the
Str 2 delay shot 1
setting elapses.
A070868 V1 EN
Figure 197:
Signal scheme of autoreclosing operation initiated with protection
operate signal
The autoreclosing shot is initiated with a trip signal of the protection function. The
autoreclosing starts when the protection operate delay time elapses.
Normally, all trip and start signals are used to initiate an autoreclosing shot and trip the
circuit breaker.
ACTIVE
output indicates reclosing sequence in progress. If any of the
input signals
INIT_X
or
DEL_INIT_X
are used for blocking, the corresponding bit
in the
Tripping line
setting must be FALSE. This is to ensure that the circuit breaker
does not trip from that signal, that is, the signal does not activate the
OPEN_CB
output.
The default value for the setting is "63", which means that all initiation signals activate
the
OPEN_CB
output. The lowest bit in the
Tripping line
setting corresponds to the
INIT_1
input, the highest bit to the
INIT_6
line.
Section 8
1MRS757454 D
Control functions
410
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......