Name
Type
Values (Range)
Unit
Description
I1_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Positive sequence
current amplitude range
I0_INST
FLOAT32
0.00...40.00
xIn
Zero sequence current
amplitude, instantaneous
value
I0_ANGL
FLOAT32
-180.00...180.00
deg
Zero sequence current
angle
I0_DB
FLOAT32
0.00...40.00
xIn
Zero sequence current
amplitude, reported value
I0_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Zero sequence current
amplitude range
7.1.9.6
Technical data
Table 438:
CSMSQI Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f/f
n
= ±2 Hz
±1.0% or ±0.002 × I
n
at currents in the range of 0.01...4.00 × I
n
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
7.1.9.7
Technical revision history
Table 439:
CSMSQI Technical revision history
Technical revision
Change
A
-
B
Sequence current angle values added to the
Monitored data view.
C
Internal improvement.
7.1.10
Sequence voltage measurement VSMSQI
7.1.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Sequence voltage measurement
VSMSQI
U1, U2, U0
U1, U2, U0
Section 7
1MRS757454 D
Measurement functions
376
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......