7.1.11.3
Signals
Table 444:
PEMMXU Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
U_A
SIGNAL
0
Phase A voltage
U_B
SIGNAL
0
Phase B voltage
U_C
SIGNAL
0
Phase C voltage
RSTACM
BOOLEAN
0=False
Reset of accumulated energy reading
7.1.11.4
Settings
Table 445:
PEMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Power unit Mult
3=Kilo
6=Mega
3=Kilo
Unit multiplier for presentation of the
power related values
Energy unit Mult
3=Kilo
6=Mega
3=Kilo
Unit multiplier for presentation of the
energy related values
Active power Dir
1=Forward
2=Reverse
1=Forward
Direction of active power flow: Forward,
Reverse
Reactive power Dir
1=Forward
2=Reverse
1=Forward
Direction of reactive power flow: Forward,
Reverse
Table 446:
PEMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Forward Wh Initial
0...999999999
1
0
Preset Initial value for forward active
energy
Reverse Wh Initial
0...999999999
1
0
Preset Initial value for reverse active
energy
Forward VArh Initial
0...999999999
1
0
Preset Initial value for forward reactive
energy
Reverse VArh Initial
0...999999999
1
0
Preset Initial value for reverse reactive
energy
Section 7
1MRS757454 D
Measurement functions
380
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......