Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the
BLOCK
input and the global setting
Configuration/System/
Blocking mode
which selects the blocking mode. The
BLOCK
input can be controlled
by a binary input, a horizontal communication input or an internal signal of the
protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode,
the operation timer is frozen to the prevailing value. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the
OPERATE
output is not activated.
4.1.4.5
Application
The motor protection during stall is primarily needed to protect the motor from
excessive temperature rise, as the motor draws large currents during the stall phase.
This condition causes a temperature rise in the stator windings. Due to reduced speed,
the temperature also rises in the rotor. The rotor temperature rise is more critical when
the motor stops.
The physical and dielectric insulations of the system deteriorate with age and the
deterioration is accelerated by the temperature increase. Insulation life is related to the
time interval during which the insulation is maintained at a given temperature.
An induction motor stalls when the load torque value exceeds the breakdown torque
value, causing the speed to decrease to zero or to some stable operating point well
below the rated speed. This occurs, for example, when the applied shaft load is
suddenly increased and is greater than the producing motor torque due to the bearing
failures. This condition develops a motor current almost equal to the value of the
locked-rotor current.
JAMPTOC is designed to protect the motor in stall or mechanical jam situations
during the running state. To provide a good and reliable protection for motors in a stall
situation, the temperature effects on the motor have to be kept within the allowed
limits.
4.1.4.6
Signals
Table 127:
JAMPTOC Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
1MRS757454 D
Section 4
Protection functions
611 series
139
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......