6.3.7
Settings
Table 392:
MDSOPT Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Warning value
0...299999
h
1
8000
Warning value for operation time
supervision
Alarm value
0...299999
h
1
10000
Alarm value for operation time supervision
Table 393:
MDSOPT Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Initial value
0...299999
h
1
0
Initial value for operation time supervision
Operating time hour
0...23
h
1
0
Time of day when alarm and warning will
occur
Operating time mode
1=Immediate
2=Timed Warn
3=Timed Warn Alm
1=Immediate
Operating time mode for warning and
alarm
6.3.8
Monitored data
Table 394:
MDSOPT Monitored data
Name
Type
Values (Range)
Unit
Description
MDSOPT
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
OPR_TIME
INT32
0...299999
h
Total operation time in
hours
6.3.9
Technical data
Table 395:
MDSOPT Technical data
Description
Value
Motor runtime measurement accuracy
1)
±0.5%
1) Of the reading, for a stand-alone relay, without time synchronization
1MRS757454 D
Section 6
Supervision functions
611 series
349
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......