A070422 V1 EN
Figure 217:
Operating effect of the
BLOCK
input when the selected blocking mode
is "Freeze timer"
If the
BLOCK
input is activated when the operate timer is running, as described in
, the timer is frozen during the time
BLOCK
remains active. If the timer
input is not active longer than specified by the
Reset delay time
setting, the operate
timer is reset in the same way as described in
, regardless of the
BLOCK
input .
The selected blocking mode is "Freeze timer".
9.2
Current based inverse definite minimum time
characteristics
9.2.1
IDMT curves for overcurrent protection
In inverse-time modes, the operation time depends on the momentary value of the
current: the higher the current, the faster the operation time. The operation time
calculation or integration starts immediately when the current exceeds the set
Start
value
and the
START
output is activated.
Section 9
1MRS757454 D
General function block features
442
611 series
Technical Manual