Parameter
Values (Range)
Unit
Step
Default
Description
Curve parameter B
0.0000...0.7120
1
0.1217
Parameter B for customer programmable
curve
Curve parameter C
0.02...2.00
1
2.00
Parameter C for customer programmable
curve
Curve parameter D
0.46...30.00
1
29.10
Parameter D for customer programmable
curve
Curve parameter E
0.0...1.0
1
1.0
Parameter E for customer programmable
curve
Table 108:
DPHLPDOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate time
20...60000
ms
1
20
Minimum operate time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Allow Non Dir
0=False
1=True
0=False
Allows prot activation as non-dir when dir
info is invalid
Min operate current
0.01...1.00
xIn
0.01
0.01
Minimum operating current
Min operate voltage
0.01...1.00
xUn
0.01
0.01
Minimum operating voltage
Table 109:
DPHHPDOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.10...40.00
xIn
0.01
0.10
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scaling the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in IEC/ANSI IDMT curves
Operating curve type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
15=IEC Def. Time
Selection of time delay curve type
Operate delay time
40...200000
ms
10
40
Operate delay time
Characteristic angle
-179...180
deg
1
60
Characteristic angle
Max forward angle
0...90
deg
1
80
Maximum phase angle in forward
direction
Max reverse angle
0...90
deg
1
80
Maximum phase angle in reverse
direction
Min forward angle
0...90
deg
1
80
Minimum phase angle in forward direction
Min reverse angle
0...90
deg
1
80
Minimum phase angle in reverse direction
Section 4
1MRS757454 D
Protection functions
126
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......