4.7.9
Technical data
Table 329:
STTPMSU Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Start time
1)2)
Minimum
Typical
Maximum
I
Fault
= 1.1 × set
Start
detection A
27 ms
30 ms
34 ms
Operate time accuracy
±1.0% of the set value or ±20 ms
Reset ratio
Typically 0.90
1) Current before = 0.0 × I
n
, f
n
= 50 Hz, overcurrent in one phase, results based on statistical distribution
of 1000 measurements
2) Includes the delay of the signal output contact
4.7.10
Technical revision history
Table 330:
STTPMSU Technical revision history
Technical revision
Change
B
Internal improvement
C
Added setting
Ini start up counter.
1MRS757454 D
Section 4
Protection functions
611 series
301
Technical Manual