Section 9
General function block features
9.1
Definite time characteristics
9.1.1
Definite time operation
The DT mode is enabled when the
Operating curve type
setting is selected either as
"ANSI Def. Time" or "IEC Def. Time". In the DT mode, the
OPERATE
output of the
function is activated when the time calculation exceeds the set
Operate delay time
.
The user can determine the reset in the DT mode with the
Reset delay time
setting,
which provides the delayed reset property when needed.
The
Type of reset curve
setting has no effect on the reset method when
the DT mode is selected, but the reset is determined solely with the
Reset delay time
setting.
The purpose of the delayed reset is to enable fast clearance of intermittent faults, for
example self-sealing insulation faults, and severe faults which may produce high
asymmetrical fault currents that partially saturate the current transformers. It is typical
for an intermittent fault that the fault current contains so called drop-off periods,
during which the fault current falls below the set start current, including hysteresis.
Without the delayed reset function, the operate timer would reset when the current
drops off. In the same way, an apparent drop-off period of the secondary current of the
saturated current transformer can also reset the operate timer.
1MRS757454 D
Section 9
General function block features
611 series
439
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......