Table 190:
DEFLPDEF Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
Table 191:
DEFHPDEF Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.2.2.11
Settings
Table 192:
DEFLPDEF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.010...5.000
xIn
0.005
0.010
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scaling the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in IEC/ANSI IDMT curves
Operating curve type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time
Selection of time delay curve type
Operate delay time
50...200000
ms
10
50
Operate delay time
Characteristic angle
-179...180
deg
1
-90
Characteristic angle
Max forward angle
0...180
deg
1
80
Maximum phase angle in forward
direction
Max reverse angle
0...180
deg
1
80
Maximum phase angle in reverse
direction
Min forward angle
0...180
deg
1
80
Minimum phase angle in forward direction
Min reverse angle
0...180
deg
1
80
Minimum phase angle in reverse direction
Voltage start value
0.010...1.000
xUn
0.001
0.010
Voltage start value
1MRS757454 D
Section 4
Protection functions
611 series
197
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......