4.1.6.8
Monitored data
Table 149:
MPTTR Monitored data
Name
Type
Values (Range)
Unit
Description
TEMP_RL
FLOAT32
0.00...9.99
The calculated
temperature of the
protected object relative
to the operate level
TEMP_AMB
FLOAT32
-99...999
°C
The ambient temperature
used in the calculation
THERMLEV_ST
FLOAT32
0.00...9.99
Thermal level at
beginning of motor
startup
THERMLEV_END
FLOAT32
0.00...9.99
Thermal level at the end
of motor startup situation
T_ENARESTART
INT32
0...99999
s
Estimated time to reset of
block restart
MPTTR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Therm-Lev
FLOAT32
0.00...9.99
Thermal level of
protected object (1.00 is
the operate level)
4.1.6.9
Technical data
Table 150:
MPTTR Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
Current measurement: ±1.5% of the set value or
±0.002 × I
n
(at currents in the range of 0.01...4.00
× I
n
)
Operate time accuracy
1)
±2.0% of the theoretical value or ±0.50 s
1) Overload current > 1.2 × Operate level temperature
4.1.6.10
Technical revision history
Table 151:
MPTTR Technical revision history
Technical revision
Change
B
Added a new input
AMB_TEMP
.
Added a new selection for the
Env temperature
mode setting "Use input".
C
Internal improvement.
D
Time constant stop range maximum value
changed from 8000 s to 60000 s.
E
Internal improvement.
Section 4
1MRS757454 D
Protection functions
160
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......