Parameter
Values (Range) Unit
Step
Default
Description
Periodic trig
time
0...604 800
s
10
0
Time between
periodic
triggerings
Stor. mode
periodic
0=Waveform
1=Trend /
cycle
1
0
Storage mode
for periodic
triggering
Stor. mode
manual
0=Waveform
1=Trend /
cycle
1
0
Storage mode
for manual
triggering
Table 452:
RDRE Non-group channel settings
Parameter
Values (Range) Unit
Step
Default
Description
Operation
1=on
5=off
1
1=on
Analog
channel is
enabled or
disabled
Channel
selection
0=Disabled
1=Io
2=IL1
3=IL2
4=IL3
10=U1
11=U2
12=U3
14=U1B
17=CIo
18=SI1
1)
19=SI2
1)
20=SU0
21=SU1
1)
22=SU2
1)
26=SUoB
27=SU1B
1)
28=SU2B
1)
0
0=Disabled
Select the
signal to be
recorded by
this channel.
Applicable
values for this
parameter are
product
variant
dependent.
Every product
variant
includes only
the values that
are applicable
to that
particular
variant
Channel id
text
0 to 64
characters,
alphanumeric
DR analog
channel X
Identification
text for the
analog
channel used
in the
COMTRADE
format
High trigger
level
0.00...60.00
pu
0.01
10.00
High trigger
level for the
analog
channel
Low trigger
level
0.00...2.00
pu
0.01
0.00
Low trigger
level for the
analog
channel
Storage mode
0=Waveform
1=Trend /
cycle
1
0
Storage mode
for the analog
channel
1) Recordable values are available only in trend mode. In waveform mode, samples for this signal type are
constant zeroes. However, these signal types can be used to trigger the recorder on limit violations of
the corresponding analog channel.
1MRS757454 D
Section 7
Measurement functions
611 series
391
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......