A070554 V1 EN
Figure 47:
Start value behavior with
ENA_MULT
input activated
Phase selection logic
If the fault criteria are fulfilled in the level detector and the directional calculation, the
phase selection logic detects the phase or phases in which the measured current
exceeds the setting. If the phase information matches the
Num of start phases
setting,
the phase selection logic activates the timer module.
Timer
Once activated, the timer activates the
START
output. Depending on the value of the
Operating curve type
setting, the time characteristics are according to DT or IDMT.
When the operation timer has reached the value of
Operate delay time
in the DT mode
or the maximum value defined by the inverse time curve, the
OPERATE
output is
activated.
When the user-programmable IDMT curve is selected, the operation time
characteristics are defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation happens, that is, a fault suddenly disappears before the operate
delay is exceeded, the timer reset state is activated. The functionality of the timer in
the reset state depends on the combination of the
Operating curve type
,
Type of reset
curve
and
Reset delay time
settings. When the DT characteristic is selected, the reset
timer runs until the set
Reset delay time
value is exceeded. When the IDMT curves are
selected, the
Type of reset curve
setting can be set to "Immediate", "Def time reset" or
"Inverse reset". The reset curve type "Immediate" causes an immediate reset. With the
1MRS757454 D
Section 4
Protection functions
611 series
111
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......