Section 13
Protection relay and functionality tests
Table 503:
Electromagnetic compatibility tests
Description
Type test value
Reference
1 MHz/100 kHz burst
disturbance test
IEC 61000-4-18
IEC 60255-26, class III
IEEE C37.90.1-2002
•
Common mode
2.5 kV
•
Differential mode
2.5 kV
3 MHz, 10 MHz and 30 MHz
burst disturbance test
IEC 61000-4-18
IEC 60255-26, class III
•
Common mode
2.5 kV
Electrostatic discharge test
IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
•
Contact discharge
8 kV
•
Air discharge
15 kV
Radio frequency interference
test
10 V (rms)
f = 150 kHz...80 MHz
IEC 61000-4-6
IEC 60255-26, class III
10 V/m (rms)
f = 80...2700 MHz
IEC 61000-4-3
IEC 60255-26, class III
10 V/m
f = 900 MHz
ENV 50204
IEC 60255-26, class III
20 V/m (rms)
f = 80...1000 MHz
IEEE C37.90.2-2004
Fast transient disturbance test
IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2002
•
All ports
4 kV
Surge immunity test
IEC 61000-4-5
IEC 60255-26
•
Communication
1 kV, line-to-earth
•
Other ports
4 kV, line-to-earth
2 kV, line-to-line
Power frequency (50 Hz)
magnetic field immunity test
IEC 61000-4-8
•
Continuous
•
1...3 s
300 A/m
1000 A/m
Table continues on next page
1MRS757454 D
Section 13
Protection relay and functionality tests
611 series
517
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......