Name
Type
Values (Range)
Unit
Description
DIR_A
Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase A
DIR_B
Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase B
DIR_C
Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase C
ANGLE_A
FLOAT32
-180.00...180.00
deg
Calculated angle
difference, Phase A
ANGLE_B
FLOAT32
-180.00...180.00
deg
Calculated angle
difference, Phase B
ANGLE_C
FLOAT32
-180.00...180.00
deg
Calculated angle
difference, Phase C
VMEM_USED
BOOLEAN
0=False
1=True
Voltage memory in use
status
DPHHPDOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.2.11
Technical data
Table 115:
DPHxPDOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the current/voltage
measured: f
n
±2 Hz
DPHLPDOC
Current:
±1.5% of the set value or ±0.002 × I
n
Voltage:
±1.5% of the set value or ±0.002 × U
n
Phase angle: ±2°
DPHHPDOC
Current:
±1.5% of the set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Voltage:
±1.5% of the set value or ±0.002 × U
n
Phase angle: ±2°
Start time
1)2)
Minimum
Typical
Maximum
I
Fault
= 2.0 × set
Start
value
39 ms
43 ms
47 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Table continues on next page
1MRS757454 D
Section 4
Protection functions
611 series
129
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......