4.2.2.7
Timer characteristics
DEFxPDEF supports both DT and IDMT characteristics. The user can select the timer
characteristics with the
Operating curve type
setting.
The protection relay provides 16 IDMT characteristics curves, of which seven comply
with the IEEE C37.112 and six with the IEC 60255-3 standard. Two curves follow the
special characteristics of ABB praxis and are referred to as RI and RD. In addition to
this, a user programmable curve can be used if none of the standard curves are
applicable. The user can choose the DT characteristic by selecting the
Operating
curve type
values "ANSI Def. Time" or "IEC Def. Time". The functionality is
identical in both cases.
The following characteristics, which comply with the list in the IEC 61850-7-4
specification, indicate the characteristics supported by different stages.
Table 184:
Timer characteristics supported by different stages
Operating curve type
DEFLPDEF
DEFHPDEF
(1) ANSI Extremely Inverse
x
x
(2) ANSI Very Inverse
x
(3) ANSI Normal Inverse
x
x
(4) ANSI Moderately Inverse
x
(5) ANSI Definite Time
x
x
(6) Long Time Extremely Inverse
x
(7) Long Time Very Inverse
x
(8) Long Time Inverse
x
(9) IEC Normal Inverse
x
(10) IEC Very Inverse
x
(11) IEC Inverse
x
(12) IEC Extremely Inverse
x
(13) IEC Short Time Inverse
x
(14) IEC Long Time Inverse
x
(15) IEC Definite Time
x
x
(17) User programmable curve
x
x
(18) RI type
x
(19) RD type
x
For a detailed description of the timers, see the
section in this manual.
1MRS757454 D
Section 4
Protection functions
611 series
185
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......