Table 95:
Measurement modes supported by DPHxPDOC stages
Measurement mode
DPHLPDOC
DPHHPDOC
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
4.1.2.6
Directional overcurrent characteristics
The forward and reverse sectors are defined separately. The forward operation area is
limited with the
Min forward angle
and
Max forward angle
settings. The reverse
operation area is limited with the
Min reverse angle
and
Max reverse angle
settings.
The sector limits are always given as positive degree values.
In the forward operation area, the
Max forward angle
setting gives the
counterclockwise sector and the
Min forward angle
setting gives the corresponding
clockwise sector, measured from the
Characteristic angle
setting.
In the backward operation area, the
Max reverse angle
setting gives the
counterclockwise sector and the
Min reverse angle
setting gives the corresponding
clockwise sector, a measurement from the
Characteristic angle
setting that has been
rotated 180 degrees.
Relay characteristic angle (RCA) is set positive if the operating current lags the
polarizing quantity and negative if the operating current leads the polarizing quantity.
1MRS757454 D
Section 4
Protection functions
611 series
113
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......