Name
Type
Values (Range)
Unit
Description
Max demand S
FLOAT32
-999999.9...9999
99.9
kVA
Maximum demand value
of apparent power
Min demand S
FLOAT32
-999999.9...9999
99.9
kVA
Minimum demand value
of apparent power
Max demand P
FLOAT32
-999999.9...9999
99.9
kW
Maximum demand value
of active power
Min demand P
FLOAT32
-999999.9...9999
99.9
kW
Minimum demand value
of active power
Max demand Q
FLOAT32
-999999.9...9999
99.9
kVAr
Maximum demand value
of reactive power
Min demand Q
FLOAT32
-999999.9...9999
99.9
kVAr
Minimum demand value
of reactive power
Time max dmd S
Timestamp
Time of maximum
demand
Time min dmd S
Timestamp
Time of minimum
demand
Time max dmd P
Timestamp
Time of maximum
demand
Time min dmd P
Timestamp
Time of minimum
demand
Time max dmd Q
Timestamp
Time of maximum
demand
Time min dmd Q
Timestamp
Time of minimum
demand
7.1.11.6
Technical data
Table 448:
PEMMXU Technical data
Characteristic
Value
Operation accuracy
At all three currents in range 0.10…1.20 × I
n
At all three voltages in range 0.50…1.15 × U
n
At the frequency f
n
±1 Hz
±1.5% for apparent power S
±1.5% for active power P and active energy
1)
±1.5% for reactive power Q and reactive energy
2)
±0.015 for power factor
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) |PF| >0.5 which equals |cosφ| >0.5
2) |PF| <0.86 which equals |sinφ| >0.5
Section 7
1MRS757454 D
Measurement functions
382
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......