In the example, the incoming feeder is carrying a load of 2.0 pu and both outgoing
feeders carry an equal load of 1.0 pu However, both HIxPDIF and HZCCxSPVC
consider the current as an increased differential or unbalance current because of the
broken CT wire in phase C. Both HIxPDIF and HZCCxSPVC receive the differential
current of approximately 1.0 pu The main differential protection HIxPDIF cannot
operate because of the higher current setting.
All CTs must have the same ratio.
The
ALARM
output of the CT supervision function can be used to energize an auxiliary
relay which can short-circuit the current CT wires, making the busbar differential
protection inoperative. This arrangement does not prevent unwanted operation of
HIxPDIF if the start setting is below the rated load. For example, if the start setting for
HIxPDIF in the example is set as 0.8 pu HIxPDIF operates before HZCCxSPVC.
6.2.7
Signals
Table 373:
HZCCASPVC Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
BLOCK
BOOLEAN
0=False
Block signal for activating blocking mode
Table 374:
HZCCBSPVC Input signals
Name
Type
Default
Description
I_B
SIGNAL
0
Phase B current
BLOCK
BOOLEAN
0=False
Block signal for activating blocking mode
Table 375:
HZCCCSPVC Input signals
Name
Type
Default
Description
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating blocking mode
Table 376:
HZCCASPVC Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm output
Table 377:
HZCCBSPVC Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm output
1MRS757454 D
Section 6
Supervision functions
611 series
343
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......