Name
Type
Values (Range)
Unit
Description
MAN_CB_CL
BOOLEAN
0=False
1=True
Indicates CB manual
closing during reclosing
sequence
SOTF
BOOLEAN
0=False
1=True
Switch-onto-fault
DARREC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
8.2.10
Technical data
Table 474:
DARREC Technical data
Characteristic
Value
Operate time accuracy
±1.0% of the set value or ±20 ms
8.2.11
Technical revision history
Table 475:
DARREC Technical revision history
Technical revision
Change
B
The
PROT_DISA
output removed and removed
the related settings
C
The default value of the
CB closed Pos status
setting changed from "True" to "False"
D
SHOT_PTR output range 0...7 (earlier 0...6)
E
Monitored data ACTIVE transferred to be ACT
visible output. SHOT_PTR output range 1...7.
F
Internal improvement
Section 8
1MRS757454 D
Control functions
438
611 series
Technical Manual