Table 258:
MNSPTOC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
BLK_RESTART
BOOLEAN
Overheated machine reconnection blocking
4.4.4.8
Settings
Table 259:
MNSPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.01...0.50
xIn
0.01
0.20
Start value
Operating curve type
5=ANSI Def. Time
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
15=IEC Def. Time
Selection of time delay curve type
Machine time Mult
5.0...100.0
0.1
5.0
Machine related time constant
Operate delay time
100...120000
ms
10
1000
Operate delay time
Table 260:
MNSPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Maximum operate time
500000...7200000
ms
1000
1000000
Max operate time regardless of the
inverse characteristic
Minimum operate time
100...120000
ms
1
100
Minimum operate time for IDMT curves
Cooling time
5...7200
s
1
50
Time required to cool the machine
Table 261:
MNSPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Current reference
0.30...2.00
xIn
0.01
1.00
Rated current (Ir) of the machine (used
only in the IDMT)
Reset delay time
0...60000
ms
1
20
Reset delay time
Section 4
1MRS757454 D
Protection functions
250
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......