The network rotating direction is set in the protection relay using the
parameter in the HMI menu:
Configuration/System/Phase rotation
.
The default parameter value is "ABC".
If the
Enable voltage limit
setting is set to "True", the magnitude of the
polarizing quantity is checked even if
Directional mode
is set to "Non-
directional" or
Allow Non Dir
to "True".
The
Characteristic angle
setting is used in the "Phase angle" mode to adjust the
operation according to the method of neutral point earthing so that in an isolated
network the
Characteristic angle
(φ
RCA
) = -90° and in a compensated network φ
RCA
= 0°. In addition, the characteristic angle can be changed via the control signal
RCA_CTL
.
RCA_CTL
affects the
Characteristic angle
setting.
The
Correction angle
setting can be used to improve selectivity due the inaccuracies
in the measurement transformers. The setting decreases the operation sector. The
correction can only be used with the "IoCos" or "IoSin" modes.
The polarity of the polarizing quantity can be reversed by setting the
Pol reversal
to
"True", which turns the polarizing quantity by 180 degrees.
For definitions of different directional earth-fault characteristics, see
the
Directional earth-fault characteristics
section in this manual.
For definitions of different directional earth-fault characteristics,
refer to general function block features information.
The directional calculation module calculates several values which are presented in
the monitored data.
Section 4
1MRS757454 D
Protection functions
176
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......