Technical revision
Change
E
Step value changed from 0.05 to 0.01 for the
Time
multiplier setting
F
Internal improvement
G
Internal improvement
4.2.2
Directional earth-fault protection DEFxPDEF
4.2.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional earth-fault protection, low
stage
DEFLPDEF
Io> ->
67N-1
Directional earth-fault protection, high
stage
DEFHPDEF
Io>> ->
67N-2
4.2.2.2
Function block
A070433 V2 EN
Figure 74:
Function block
4.2.2.3
Functionality
The directional earth-fault protection function DEFxPDEF is used as directional
earth-fault protection for feeders.
The function starts and operates when the operating quantity (current) and polarizing
quantity (voltage) exceed the set limits and the angle between them is inside the set
operating sector. The operate time characteristic for low stage (DEFLPDEF) and high
stage (DEFHPDEF) can be selected to be either definite time (DT) or inverse definite
minimum time (IDMT).
In the DT mode, the function operates after a predefined operate time and resets when
the fault current disappears. The IDMT mode provides current-dependent timer
characteristics.
Section 4
1MRS757454 D
Protection functions
172
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......