4.4.1.7
Settings
Table 235:
NSPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.01...5.00
xIn
0.01
0.30
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scaling the start value
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in IEC/ANSI IDMT curves
Operate delay time
40...200000
ms
10
40
Operate delay time
Operating curve type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time
Selection of time delay curve type
Table 236:
NSPTOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Table 237:
NSPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Curve parameter A
0.0086...120.0000
1
28.2000
Parameter A for customer programmable
curve
Curve parameter B
0.0000...0.7120
1
0.1217
Parameter B for customer programmable
curve
Curve parameter C
0.02...2.00
1
2.00
Parameter C for customer programmable
curve
Curve parameter D
0.46...30.00
1
29.10
Parameter D for customer programmable
curve
Curve parameter E
0.0...1.0
1
1.0
Parameter E for customer programmable
curve
Section 4
1MRS757454 D
Protection functions
232
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......