time. As no reboot is necessary, the time synchronization starts immediately after the
IRIG-B sync source is selected and the IRIG-B signal source is connected.
IRIG-B time synchronization requires a COM card with an IRIG-B
input.
3.5.1.3
Signals
Table 29:
GNRLLTMS output signals
Name
Type
Description
ALARM
BOOLEAN
Time synchronization alarm
WARNING
BOOLEAN
Time synchronization warning
3.5.1.4
Settings
Table 30:
Time format
Parameter
Values (Range)
Unit
Step
Default
Description
Time format
1=24H:MM:SS:MS
2=12H:MM:SS:MS
1=24H:MM:SS:M
S
Time format
Date format
1=DD.MM.YYYY
2=DD/MM/YYYY
3=DD-MM-YYYY
4=MM.DD.YYYY
5=MM/DD/YYYY
6=YYYY-MM-DD
7=YYYY-DD-MM
8=YYYY/DD/MM
1=DD.MM.YYYY
Date format
Table 31:
Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Synch source
0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
1=SNTP
Time synchronization source
PTP domain ID
0...255
1
0
The domain is identified by an integer, the
domainNumber, in the range of 0 to 255.
PTP priority 1
0...255
1
128
PTP priority 1, in the range of 0 to 255.
PTP priority 2
0...255
1
128
PTP priority 2, in the range of 0 to 255.
PTP announce mode
1=Basic IEEE1588
2=Power Profile
1=Basic IEEE1588 PTP announce frame mode
1MRS757454 D
Section 3
Basic functions
611 series
57
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......