8.1.8
Monitored data
Table 462:
CBXCBR Monitored data
Name
Type
Values (Range)
Unit
Description
POSITION
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus position
indication
8.1.9
Technical revision history
Table 463:
CBXCBR Technical revision history
Technical revision
Change
B
Interlocking bypass input (
ITL_BYPASS
) and
opening enabled (
OPEN_ENAD
)/closing enabled
(
CLOSE_ENAD
) outputs added.
ITL_BYPASS
bypasses the
ENA_OPEN
and
ENA_CLOSE
states.
C
Internal improvement.
D
Added inputs
TRIP
and
SYNC_OK
. Renamed input
ITL_BYPASS
to
SYNC_ITL_BYP
. Added outputs
CL_REQ
and
OP_REQ
. Outputs
OPENPOS
and
CLOSEPOS
are forced to “FALSE” in case status is
Faulty (11).
8.2
Autoreclosing DARREC
8.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Autoreclosing
DARREC
O -> I
79
1MRS757454 D
Section 8
Control functions
611 series
403
Technical Manual